module XPSVN - zero speed detection - 24 V DC for motor power supply <= 60 Hz
- Produttore:
- Schneider Electric
This XPSVNE safety module is for zero-speed detection. It meets the requirements of PL c/Category 2 conforming to EN/ISO 13849-1.and SILCL1 conforming to EN/IEC 61508 and EN/IEC 62061. Used in conjunction with XU2S single-beam photo-electric sensors (periodically tested), it establishes a category 2 light curtain conforming to IEC/EN 61496 parts 1 and 2. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has additional solid-state output for communication with PLCs about safety status of your process.
Specifications
Certifications | CSA |
---|---|
Depth | 114 mm |
Height | 99 mm |
Input Voltage | 500 V |
Net Weight | 0.5 kg |
Standard | EN/IEC 60204-1 |
Storage Temperature | -25-85 °C |
Warranty Length | 18 months |
Width | 45 mm |
Specifications | |
Product Certifications | CSA || UL || TÜV |
Function Of Module | monitoring 3-phase motor with star-delta starting || monitoring 3-phase motor with variable number of poles and star-delta starting || monitoring 3-phase motor + variable speed drive || monitoring 3-phase motor || monitoring XPS AK || monitoring star-delta motor starter and guard switch type XCS E || monitoring dc motor |
Safety Level | can reach PL d/category 3 EN/ISO 13849-1 || can reach SILCL 2 EN/IEC 62061 |
[Us] Rated Supply Voltage | 24 V DC - 15...10 % |
Range Of Product | Preventa Safety automation |
Product Or Component Type | Preventa safety module |
Safety Module Name | XPSVNE |
Number Of Additional Circuits | 2 solid state outputs |
Output Type | relay, 1 NO + 1 NC, volt-free |
Safety Module Application | for zero speed detection |
Safety Reliability Data | MTTFd = 124.1 years EN/ISO 13849-1 || DC > 99 % EN/ISO 13849-1 || PFHd = 9.26E-9 1/h EN/IEC 62061 |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Product Destination | for motor power supply <= 60 Hz |
[Uimp] Rated Impulse Withstand Voltage | 4 kV III IEC 60947-5-1 || 4 kV III DIN VDE 0110 parts 1 and 2 |
Net Weight | 0.5 kg |
Standards | EN/IEC 60947-5-1 || EN/IEC 60204-1 |
[Ui] Rated Insulation Voltage | 300 V 2)IEC 60947-5-1 || 300 V 2)DIN VDE 0110 parts 1 and 2 |
Input Voltage | 500 Vrms |
Connections - Terminals | captive screw clamp terminals, removable terminal block flexible 0.2...1.5 mm² without cable end, 2 wires || captive screw clamp terminals, removable terminal block flexible 0.2...2.5 mm² without cable end, 1 wire || captive screw clamp terminals, removable terminal block flexible 0.25...1 mm² with cable end, without bezel, 2 wires || captive screw clamp terminals, removable terminal block flexible 0.25...2.5 mm² with cable end, with bezel, 1 wire || captive screw clamp terminals, removable terminal block flexible 0.25...2.5 mm² with cable end, without bezel, 1 wire || captive screw clamp terminals, removable terminal block flexible 0.5...1.5 mm² with cable end, with double bezel, 2 wires || captive screw clamp terminals, removable terminal block solid 0.2...1 mm² without cable end, 2 wires || captive screw clamp terminals, removable terminal block solid 0.2...2.5 mm² without cable end, 1 wire |
Width | 45 mm |
Depth | 114 mm |
Input Detection Threshold | 0.01...0.1 V |
Breaking Capacity | 1.2 A 24 V DC-13)50 ms NC relay output circuit || 1.5 A 24 V DC-13)50 ms NO relay output circuit || 10 mA 48 V solid state output circuit || 20 mA 24 V solid state output circuit |
Height | 99 mm |
Breaking Capacity | 180 VA holding AC-15 C300 relay output || 1800 VA inrush AC-15 C300 relay output |
[Ith] Conventional Free Air Thermal Current | 2.5 A relay output |
Mounting Support | 35 mm symmetrical DIN rail |
Power Consumption In W | 3.5 W |
Minimum Output Voltage | 17 V relay output |
Minimum Output Current | 10 mA relay output |
Associated Fuse Rating | 4 A gG relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200 |
Local Signalling | 4 LEDs |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Circularity Profile | ENVEOLI1406024EN |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1406024EN |
Sustainable Offer Status | Green Premium product |
Pvc Free | Yes |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | X |
Environment | |
Ambient Air Temperature For Operation | -10-55 °C |
Ip Degree Of Protection | IP20 terminals)EN/IEC 60529 || IP40 enclosure)EN/IEC 60529 |
Ambient Air Temperature For Storage | -25-85 °C |