PRO ECO 960W 24V 40A

Produttore:
WEIDMULLER
Weidmüller

B06576a8a694f436e6edfec2932d39d52e02da7b medium
Prezzo (IVA esclusa)
€ 230.40
Codice Nuova Elva
1469520000
Codice produttore
1469520000
Disponibilità
Invia RdO

Power supply, switch-mode power supply unit, 24 V

Specifications

Depth120 mm
Height125 mm
IP RatingIP20
Max. Operating Temperature70 °C
Min. Operating Temperature-25 °C
Net Weight3,190 g
Operating Temperature-25 °C...70 °C
Storage Temperature-40 °C...85 °C
Width160 mm

Dimensions And Weights

Width160 mm
Width (inches)6.299 inch
Height125 mm
Height (inches)4.921 inch
Depth120 mm
Depth (inches)4.724 inch
Net weight3,190 g

Temperatures

Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.85 °C
Storage temperature, min.-40 °C
Operating temperature-25 °C...70 °C
Storage temperature-40 °C...85 °C

Environmental Product Compliance

REACH SVHCLead 7439-92-1

Input

AC current consumption4,6 A @ 230 V AC / 9,9 A @ 110 V AC
Rated input voltage100...240 V AC (wide-range input)
Recommended back-up fuse16 A / DI, safety fuse20 A, Char. B, circuit breaker16 A, Char. C, circuit breaker
Surge protectionVaristor
AC input voltage range85...264 V AC (derating at 100 V AC)
Connection systemScrew connection
DC current consumption2,9 A @ 370 V DC / 9 A @ 120 V DC
DC input voltage range80...370 V DC (Derating @ 120 V DC)
Frequency range AC47...63 Hz
Input frequency47...63 Hz
Input fuse (internal)Yes
Inrush currentmax. 5 A

Output

Capacitive loadunrestricted
Ramp-up time≤ 100 ms
Rated output voltage24 V DC ± 1 %
Residual ripple, breaking spikes< 50 mVPP @ 24 V DC, IN
Connection systemScrew connection
Continous output current @ U40 A @ 50 °C, 24 A @ 70 °C
Nominal output current for U40 A @ 50 °C
Output power960 W
Output voltage22...28 V (adjustable via potentiometer)
Overload protectionYes
Parallel connection optionyes, max. 3
Protection against inverse voltageYes

General Data

AC failure bridging time @ I> 20 ms @ 230 V AC / > 20 ms @ 115 V AC
Power factor (approx.)> 0.98…230 V AC / > 0.98…115 V AC
Power loss, idling8 W
Power loss, nominal load85 W
Protection against over-heatingYes
Protection against reverse voltages from the load30…35 V DC
Protection degreeIP20
Short-circuit protectionYes
Degree of efficiency93%
Earth leakage current, max.3.5 mA
Housing versionMetal, corrosion resistant
IndicationGreen LED (Uoutput > 21.6 V DC), Yellow LED (loutput > 90 % IRated typ. ), red LED (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
MTBF> 500,000 h in accordance with IEC 61709 (SN29500)
Max. perm. air humidity (operational)5 %…95 % RH
Mounting position, installation noticeon terminal rail TS 35
Operating temperature-25 °C...70 °C

Emc / Shock / Vibration

Limiting of mains voltage harmonic currentsAccording to EN 61000-3-2
Noise emission in accordance with EN55032Class B
Vibration resistance IEC 60068-2-61 g according to EN 50178
Interference immunity test acc. toEN 61000-4-2 (ESD), EN 61000-4-3 (RS), EN 61000-4-4 (burst), EN 61000-4-5 (surge), EN 61000-4-6 (conducted), EN61000-4-8 (Fields), EN61000-4-11 (Dips)
Shock resistance IEC 60068-2-2715 g In all directions

Insulation Coordination

Insulation voltage input / earth2 kV
Insulation voltage output / earth0.5 kV
Insulation voltage, input/output3 kV
Pollution severity2
Protection classI, with PE connection

Electrical Safety (Applied Standards)

Electrical machine equipmentAcc. to EN60204
For use with electronic equipmentAcc. to EN50178 / VDE0160
Protection against dangerous shock currentsAcc. to VDE0106-101
Protective separation / protection against electrical shockVDE0100-410 / acc. to DIN57100-410
Safety extra-low voltageSELV according to EN 60950, PELV according to EN 60204
Safety transformers for switch-mode power suppliesAccording to EN 61558-2-16

Connection Data (Input)

Conductor cross-section, AWG/kcmil , max.12
Wire connection cross section, flexible (input), max.2.5 mm²
Conductor cross-section, AWG/kcmil , min.26
Conductor cross-section, flexible , min.0.5 mm²
Conductor cross-section, rigid , max.6 mm²
Conductor cross-section, rigid , min.0.5 mm²
Connection systemScrew connection
Number of terminals3 for L/N/PE
Tightening torque, max.0.6 Nm
Tightening torque, min.0.5 Nm

Connection Data (Output)

Conductor cross-section, AWG/kcmil , max.8
Tightening torque, min.0.5 Nm
Conductor cross-section, AWG/kcmil , min.22
Conductor cross-section, flexible , max.10 mm²
Conductor cross-section, flexible , min.2.5 mm²
Conductor cross-section, rigid , max.16 mm²
Conductor cross-section, rigid , min.0.5 mm²
Connection systemScrew connection
Number of terminals7 (++,---,13,14)
Tightening torque, max.0.6 Nm

Signalling

Contact load (NO contact)max. 30 V DC / 1 A
Floating contactYes
Relay on/offOutput voltage >21.6 V DC/ <20.4 V DC, overload

Approvals

ApprovalsCE, CULUS, EAC, TUEV
ROHSConform
UL File Number SearchE258476

Ratings Iecex/Atex/Cul

Certificate no. (cULus)E258476

Classifications

ETIM 6.0EC002540
ETIM 7.0EC002540
eClass 9.027-04-07-01
eClass 9.127-04-07-01
eClass 10.027-04-07-01

Documentazione


Spesso acquistati assieme


Altri articoli da WEIDMULLER

Richiedi un preventivo