TOPJOB®S triple-deck terminal block; through/through/through (L/L/L); with marker carrier; rail mount; 2-conductor; 5.2 mm wide; gray
- Produttore:
- WAGO
Features
American Bureau of Shipping, ABS, 20-HG1941090-PDA, EN 60947
Underwriters Laboratories Inc., AEx, E185892, UL 60079
DEKRA Certification B.V., CSA, 1536069, C22.2 No. 158
DEKRA Certification B.V., CCA, 71-120369, EN 60947
TÜV Rheinland do Brasil Ltda., INMETRO, TÜV 12.1307 U, IEC 60079
DEKRA Certification B.V., CCA, NTR NL 7892, EN 60947
CNEX, CCC, 2020312313000238, GB/T 3836.3
Bureau Veritas S.A., BV, 38586/B0 BV, EN 60947
Det Norske Veritas, Germanischer Lloyd, DNV GL, TAE00001V2
Brjansker Zertifizierungsstelle, EAC, RU C-DE.AM02.B.00127/19, TP TC 012/2011
Physikalisch Technische Bundesanstalt (PTB), ATEX, PTB 03 ATEX 1162 UII2G Ex eb IIC Gb, IM2 Ex eb IMb, EN 60079
Underwriters Laboratories Inc., UL, E45172, UL 1059
WAGO GmbH & Co. KG, Railway, Railway Ready
American Bureau of Shipping, ABS, 20-HG1941090-PDA, EN 60947
Underwriters Laboratories Inc., AEx, E185892, UL 60079
DEKRA Certification B.V., CSA, 1536069, C22.2 No. 158
DEKRA Certification B.V., CCA, 71-120369, EN 60947
TÜV Rheinland do Brasil Ltda., INMETRO, TÜV 12.1307 U, IEC 60079
DEKRA Certification B.V., CCA, NTR NL 7892, EN 60947
CNEX, CCC, 2020312313000238, GB/T 3836.3
Bureau Veritas S.A., BV, 38586/B0 BV, EN 60947
Det Norske Veritas, Germanischer Lloyd, DNV GL, TAE00001V2
Brjansker Zertifizierungsstelle, EAC, RU C-DE.AM02.B.00127/19, TP TC 012/2011
Physikalisch Technische Bundesanstalt (PTB), ATEX, PTB 03 ATEX 1162 UII2G Ex eb IIC Gb, IM2 Ex eb IMb, EN 60079
Underwriters Laboratories Inc., UL, E45172, UL 1059
WAGO GmbH & Co. KG, Railway, Railway Ready
Specifications
Actuator | Operating Tool |
---|---|
Color | Gray |
Conductor Material | Copper |
Conductor Size | 12 AWG |
Country of Origin | Germany |
Current | 20 A |
Flammability Class | V0 |
Height | 3.673 in |
Insulation Material | Polyamide |
Mounting Type | DIN-35 Rail |
Number of Connections | 3 |
Operating Temperature | 105 °C |
Package Type | Box |
Strip Length | 0.47 in |
Voltage | 300 V |
Weight | 17.528 g |
Width | 0.205 in |
Specifications | |
Product Group Code | 0022 |
Ratings Per Iec/En | |
Ratings per | IEC/EN 60947-7-1 |
Nominal voltage (III/3) | 500 V |
Rated impulse voltage (III/3) | 6 kV |
Rated current | 24 A |
Current at conductor cross-section (max.) mm² | 28 A |
Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
Ratings Per Ul 1059 | |
Approvals per | UL 1059 |
Rated voltage UL (Use Group B) | 300 V |
Rated current UL (Use Group B) | 20 A |
Rated voltage UL (Use Group C) | 300 V |
Rated current UL (Use Group C) | 20 A |
Rated voltage UL (Use Group D) | 600 V |
Rated current UL (Use Group D) | 5 A |
Ratings Per Csa | |
Approvals per | CSA 22.2 No 158 |
Rated voltage CSA (Use Group B) | 600 V |
Rated current CSA (Use Group B) | 20 A |
Rated voltage CSA (Use Group C) | 600 V |
Rated current CSA (Use Group C) | 20 A |
Ex Information | |
Reference hazardous areas | See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications” |
Ratings per | ATEX: PTB 03 ATEX 1162 U / IECEx: PTB 03.0004U (Ex eb IIC Gb) |
Rated voltage EN (Ex e II) | 440 V |
Rated current (Ex e II) | 19 A |
Rated current (Ex e II) with jumper | 17 A |
Power Loss | |
Power loss, per pole (potential) | 0.7661 W |
Rated current IN for specified power loss | 24 A |
Resistance value for specified, current-dependent power loss | 0.00133 Ω |
Connection 1 | |
Connection technology | Push-in CAGE CLAMP® |
Fine-stranded conductor; with ferrule; push-in termination | 1 … 2.5 mm² / 18 … 14 AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
Strip length | 10 … 12 mm / 0.39 … 0.47 inches |
Wiring direction | Front-entry wiring |
Number of connection points | 3 |
Actuation type | Operating tool |
Connectable conductor materials | Copper |
Nominal cross-section | 2.5 mm² |
Solid conductor | 0.25 … 4 mm² / 22 … 12 AWG |
Solid conductor; push-in termination | 0.75 … 4 mm² / 18 … 12 AWG |
Fine-stranded conductor | 0.25 … 4 mm² / 22 … 12 AWG |
Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5 mm² / 22 … 14 AWG |
Connection 2 | |
Number of connection points 2 | 3 |
Physical Data | |
Width | 5.2 mm / 0.205 inches |
Height | 93.3 mm / 3.673 inches |
Depth from upper-edge of DIN-rail | 81.3 mm / 3.201 inches |
Mechanical Data | |
Potential marking | L/L/L |
Mounting type | DIN-35 rail |
Marking level | Center/side marking |
Material Data | |
Note (material data) | <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a> |
Color | Gray |
Material group | I |
Insulation material | Polyamide (PA66) |
Flammability class per UL94 | V0 |
Fire load | 0.336 MJ |
Weight | 17.528 g |
Environmental Requirements | |
Processing temperature | -35 … +85 °C |
Continuous operating temperature | -60 … +105 °C |
Commercial Data | |
Packaging type | Box |
Country of origin | DE |
GTIN | 4044918989756 |
Customs tariff number | 85369010000 |