Configurable temperature transducer with plug-in connection technology for connecting thermocouples. Configurable via DIP switch or software. Screw connection technology, standard configuration
Features
cULus Listed
ATEX
GL
UL Listed
cUL Listed
Specifications
Depth | 119.2 mm |
---|---|
Height | 109.81 mm |
Strip Length | 10 mm |
Width | 6.2 mm |
Ambient conditions | |
Ambient temperature (operation) | -40 °C - 70 °C |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Permissible humidity (operation) | 5 % - 95 % (non-condensing) |
Degree of protection | IP20 (not assessed by UL) |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Input data | |
Configurable/programmable | Yes |
Sensor types that can be used (TC) | B, C, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L |
Temperature measuring range | -250 °C - 2500 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 1350°C via DIP switches) |
Power supply | |
Supply voltage range | 9.6 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Typical current consumption | 32.7 mA (24 V DC) |
Typical current consumption | 66.8 mA (12 V DC) |
Power consumption | ≤ 850 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load) |
Dimensions | |
Width | 6.2 mm |
Height | 109.81 mm |
Depth | 119.2 mm |
Output data | |
Number of outputs | 1 |
Configurable/programmable | Yes |
Voltage output signal | 0 V - 5 V (via DIP switch) |
Voltage output signal | 1 V - 5 V (via DIP switch) |
Voltage output signal | 0 V - 10 V (via DIP switch) |
Voltage output signal | 10 V - 0 V (via DIP switch) |
Voltage output signal | 0 V - 10.5 V (can be set via software) |
Current output signal | 0 mA - 20 mA (via DIP switch) |
Current output signal | 4 mA - 20 mA (via DIP switch) |
Current output signal | 20 mA - 0 mA (via DIP switch) |
Current output signal | 20 mA - 4 mA (via DIP switch) |
Current output signal | 0 mA - 21 mA (can be set via software) |
Max. output voltage | approx. 12.3 V |
Max. output current | 24.6 mA |
Short-circuit current | < 31.5 mA |
Load/output load voltage output | ≥ 10 kΩ |
Load/output load current output | ≤ 600 Ω (at 20 mA) |
Ripple | < 10 mVrms |
Ripple | < 10 mVrms (at 600 Ω) |
Connection data | |
Connection method | Screw connection |
Stripping length | 10 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² - 1.5 mm² (with ferrule) |
Conductor cross section solid | 0.14 mm² - 2.5 mm² (without ferrule) |
Conductor cross section flexible | 0.14 mm² - 2.5 mm² |
Conductor cross section AWG | 24 - 12 (flexible) |
Torque | 0.5 Nm - 0.6 Nm |
EMC data | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 0.06 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 0.1 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 0.05 % |
Standards and Regulations | |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Standards/regulations | EN 61000-4-4 |
Standards/regulations | EN 61000-4-5 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Listed |
UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D T6 |
UL, USA/Canada | Class I, Zone 2, Group IIC T6 |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |