module XPSAC - Emergency stop - 24 V AC DC

Manufactured by:
Schneider Electric
Schneider electric

3da6dc70800dd086b6a6d97c602f41731c747713 medium
Nuova Elva code
XPSAC5121
Manufacturer code
XPSAC5121
Availability
Send request for quotation

This XPSAC safety module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of Performance Level PL e/Category 4 conforming to standard EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring emergency stop circuits conforming to standards EN/ISO 13850 and EN/IEC 60204-1. 24V AC/DC supply allows direct supply via an auxiliary transformer, like ABT7 or ABL6, allowing saving at installation time. It has additional solid-state output for communication with PLCs about safety status of your process.

Specifications

CertificationsCSA
Current24 V
Net Weight0.16 kg
StandardEN 1088/ISO 14119
Storage Temperature-25-85 °C
Warranty Length18 months

Specifications

[Us] Rated Supply Voltage24 V AC - 20...10 % || 24 V DC - 20...20 %
Safety Reliability DataMTTFd = 210.4 years EN/ISO 13849-1 || DC > 99 % EN/ISO 13849-1 || PFHd = 3.56E-9 1/h EN/IEC 62061
Function Of Moduleemergency stop || switch monitoring
Safety Levelcan reach PL e/category 4 EN/ISO 13849-1 || can reach SILCL 3 EN/IEC 62061
Range Of ProductPreventa Safety automation
Product Or Component TypePreventa safety module
Safety Module NameXPSAC
Type Of Startunmonitored
Output Typerelay instantaneous opening, 3 NO, volt-free
Connections - Terminalscaptive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible without cable end || captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² solid without cable end || captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezel || captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel || captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² flexible without cable end || captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² solid without cable end || captive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel || captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
Number Of Additional Circuits1 solid state output
Safety Module Applicationfor emergency stop and switch monitoring

Contractual warranty

Warranty18 months

Complementary

[Uc] Control Circuit Voltage24 V
Net Weight0.16 kg
[Ui] Rated Insulation Voltage300 V 2)IEC 60947-5-1 || 300 V 2)DIN VDE 0110 part 1
Local Signalling2 LEDs
Breaking Capacity1.5 A 24 V DC-13)50 ms relay output
Maximum Power Consumption In Va2.5 VA AC
Maximum Power Consumption In W1.2 W DC
Supply Frequency50/60 Hz
Maximum Response Time On Input Open100 ms
Breaking Capacity180 VA holding AC-15 C300 relay output || 1800 VA inrush AC-15 C300 relay output
Mounting Support35 mm symmetrical DIN rail
Output Thermal Current6 A per relay relay output
Minimum Output Voltage16 V relay output
Current Consumption40 mA 24 V DC on power supply || 90 mA 24 V AC on power supply
Minimum Output Current10 mA relay output
[Ith] Conventional Free Air Thermal Current10.5 A
Associated Fuse Rating4 A gG or gL relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200 || 6 A fast blow relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200
[Uimp] Rated Impulse Withstand Voltage4 kV III IEC 60947-5-1 || 4 kV III DIN VDE 0110 part 1

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI1406024EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Mercury FreeYes
Environmental DisclosureENVPEP1406024EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX

Environment

Product CertificationsUL || CSA || TÜV
Ambient Air Temperature For Operation-10-55 °C
StandardsEN/IEC 60947-5-1 || EN/ISO 13850 || EN 60204-1 || EN 1088/ISO 14119
Ip Degree Of ProtectionIP20 terminals)EN/IEC 60529 || IP40 enclosure)EN/IEC 60529
Ambient Air Temperature For Storage-25-85 °C

Docs


Frequently bought together


Similar items


Request a quote