Uninterruptible power supply - QUINT-UPS/ 24DC/ 24DC/20 - 2320238
- Produttore:
- PHOENIX CONTACT
Uninterruptible power supply with IQ technology for DIN rail mounting, input: 24 V DC, output: 24 V DC/20 A, including mounted universal DIN rail adapter UTA 107/30
Features
Easy handling thanks to automatic battery detection, tool-free battery replacement during operation, and communication via the IFS interface
Optimum use of the buffer time and preventive monitoring of the energy storage
Rapid battery charging
Comprehensive signaling and parameterization
Fast tripping of standard circuit breakers with SFB (selective fuse breaking) technology
Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
BV
cULus Listed
EAC
cULus Recognized
LR
PRS
DNV GL
ABS
UL Listed
cUL Listed
UL Recognized
cUL Recognized
Specifications
Depth | 125 mm |
---|---|
Height | 130 mm |
Output Voltage | 24 V |
Strip Length | 8 mm |
Voltage | 10 V |
Width | 40 mm |
Output data (24 V DC battery operation) | |
Nominal output voltage | 24 V DC |
Output voltage range (depends on the input voltage) | 19.2 V DC - 27.6 V DC (UOUT = UBAT - 0.5 V DC) |
Nominal output current (IN) | 20 A (-25 °C - 60 °C) |
POWER BOOST (IBoost) | 27 A (-25°C - 40°C) |
Selective Fuse Breaking (ISFB) | 120 A (-25 °C - 60 °C) |
Output data (24 V DC mains operation) | |
Nominal output voltage | 24 V DC |
Output voltage range (depends on the input voltage) | 18 V DC - 30 V DC |
Nominal output current (IN) | 20 A (-25 °C - 60 °C) |
POWER BOOST (IBoost) | 26 A (-25°C - 40°C) |
Selective Fuse Breaking (ISFB) | 120 A (-25 °C - 60 °C) |
Conformance/approvals | |
UL approvals | UL Listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
UL approvals | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 25; |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Standards | |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Rail applications | EN 50121-4 |
Dimensions | |
Width | 40 mm |
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 123 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 43 mm |
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
EMC data | |
Voltage | 10 V (Test Level 3) |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Electromagnetic HF field | EN 61000-4-3 |
Frequency range | 80 MHz - 1 GHz |
Test field strength | 20 V/m |
Frequency range | 1 GHz - 3 GHz |
Test field strength | 10 V/m |
Frequency range | 2 GHz - 3 GHz |
Test field strength | 3 V/m |
Comments | Criterion A |
Fast transients (burst) | EN 61000-4-4 |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Surge voltage load (surge) | EN 61000-4-5 |
Input | 1 kV (Test Level 2 - symmetrical) |
Output | 1 kV (Test Level 2 - symmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz - 80 MHz |
Input data | |
Input voltage | 24 V DC |
Nominal input voltage | 24 V DC |
Input voltage range | 18 V DC - 30 V DC |
Current consumption (maximum) | 32.9 A (maximum, mains operation) |
Current consumption (charging process) | 6.9 A (Charging, mains operation) |
Fixed backup threshold | ≤ 22 V DC |
Variable connect threshold | 1 V/0.1 s |
Connection data, input | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 12 |
Conductor cross section AWG max. | 10 |
Stripping length | 8 mm |
Screw thread | M4 |
Connection data, output | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 12 |
Conductor cross section AWG max. | 10 |
Stripping length | 8 mm |
Screw thread | M4 |
Ambient conditions | |
Ambient temperature (operation) | -25 °C - 70 °C |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of protection | IP20 |
Connection data for signaling | |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 4 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M4 |
General output data | |
Efficiency | > 98 % (Mains operation, with charged energy storage) |