Inline function terminal - IB IL TEMP 2 RTD-PAC - 2861328
- Produttore:
- PHOENIX CONTACT
Inline, Temperature measurement terminal, Analog RTD inputs: 2, connection method: 2, 3, 4-wire, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
Features
Two inputs for resistive temperature sensors
Pt, Ni, Cu, KTY sensor types according to DIN and SAMA
Connection of sensors in 2, 3, and 4-wire technology
The channels are parameterized independently of one another via the bus system
Measured values can be represented in three different formats
Measured value acquisition with 16-bit resolution
BV
BSH
EAC
ATEX
LR
RINA
DNV GL
ABS
UL Listed
cUL Listed
UL Recognized
Specifications
Depth | 71.5 mm |
---|---|
Height | 136.8 mm |
Width | 12.2 mm |
Environmental Product Compliance | |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Dimensions | |
Width | 12.2 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Interfaces | |
Designation | Inline local bus |
No. of channels | 2 |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Analog inputs | |
Number of inputs | 2 |
Input name | Analog RTD inputs |
Description of the input | Input for resistive temperature sensors |
Connection method | Spring-cage connection |
Connection technology | 2, 3, 4-wire |
Note regarding the connection technology | shielded |
Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors, linear resistors |
Linear resistance measuring range | 0 Ω - 400 Ω |
Linear resistance measuring range | 0 Ω - 4 kΩ |
Measuring principle | Successive approximation |
Measured value representation | 16 bit two's complement |
A/D conversion time | typ. 120 µs (per channel) |
A/D converter resolution | 16 bit |
Process data update | 32 ms (both channels with 3-wire technology) |
Ambient conditions | |
Air pressure (operation) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Air pressure (operation) | 80 kPa - 106 kPa (up to 3000 m above sea level, in ATEX Zone 2) |
Air pressure (storage/transport) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 55 °C |
Ambient temperature (storage/transport) | -25 °C - 85 °C |
Permissible humidity (operation) | 10 % - 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % - 95 % (non-condensing) |
Inline potentials | |
Designation | Communications power (UL) |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current consumption | typ. 43 mA |
Current consumption | max. 60 mA |
Designation | Supply of analog modules (UANA) |
Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC - 30 V DC (including all tolerances, including ripple) |
Current consumption | typ. 11 mA |
Current consumption | max. 18 mA |
Power consumption | typ. 587 mW |
Standards and Regulations | |
Connection in acc. with standard | CUL |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
Electrical isolation | |
Test section | 7.5 V supply (bus logics)/24 V analog supply (analog I/O) 500 V AC 50 Hz 1 min. |
Test section | 7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 1 min. |
Test section | 24 V analog supply (analog I/O) / functional earth ground 500 V AC 50 Hz 1 min. |