Power supply unit 2866404

Produttore:
PHOENIX CONTACT
Phoenix contact

0d4360d55e6d7a9b5f84143fff7a593115401739 medium
Prezzo (IVA esclusa)
€ 528.29
Codice Nuova Elva
2866404
Codice produttore
2866404
Disponibilità
Invia RdO

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 3-phase, output: 24 V DC/40 A

Features

  • Use the third negative terminal block as a grounding terminal block and minimize installation costs

  • Rugged design with metal housing and wide temperature range from -25 to +70°C

  • Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to 300 V AC

  • Compensation of voltage drops by means of output voltage that can be adjusted on the front

  • cULus Listed

  • EAC

  • cULus Recognized

  • EAC

  • UL Listed

  • cUL Listed

  • UL Recognized

  • cUL Recognized

Specifications

Height130 mm
Operating Temperature-25 °C
Protection RatingIP20
Width139 mm

Output data

Nominal output voltage24 V DC ±1 %
Setting range of the output voltage (U<sub>Set</sub>)22.5 V DC - 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (I<sub>N</sub>)40 A (-25 °C - 55 °C)
Derating55 °C - 70 °C (2.5%/K)
Connection in parallelYes, for redundancy and increased capacity
Connection in seriesyes
Feedback resistance35 V DC
Protection against surge voltage on the output< 35 V DC
Max. capacitive loadunlimited
Active current limitationApprox. 48 A
Control deviation< 1 % (change in load, static 10 % - 90 %)
Control deviation< 2 % (change in load, dynamic 10 % - 90 %)
Control deviation< 0.1 % (change in input voltage ±10 %)
Residual ripple< 20 mVPP
Output power960 W
Typical response time< 1 s
Peak switching voltages nominal load< 40 mVPP
Maximum power dissipation in no-load condition16 W
Power loss nominal load max.91 W

Standards and Regulations

Standard – Protection against shock currents, basic requirements for protective separation in electrical equipmentEN 50178
Standard – Limitation of mains harmonic currentsEN 61000-3-2
UL approvalsUL/C-UL listed UL 508
UL approvalsUL/C-UL Recognized UL 60950-1
Shock15g in all directions in acc. with IEC 60068-2-27
Vibration (operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (operation)15 Hz - 150 Hz, 2.3g, 90 min.
Rail applicationsEN 50121-4
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Noise immunityEN 61000-6-2:2005
Connection in acc. with standardCUL
Standards/regulationsEN 61000-4-2
Contact discharge4 kV (Test Level 2)
Standards/regulationsEN 61000-4-3
Frequency range80 MHz - 1 GHz
Test field strength10 V/m
Frequency range1.4 GHz - 2 GHz
Test field strength3 V/m
Standards/regulationsEN 61000-4-4
CommentsCriterion B
Standards/regulationsEN 61000-6-3
Standards/regulationsEN 61000-4-6
Frequency range0.15 MHz - 80 MHz
Voltage10 V (Test Level 3)
Standards/regulationsEN 61000-4-11
Low Voltage DirectiveConformance with LV directive 2006/95/EC
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltageEN 60950-1 (SELV)
Standard – Safety extra-low voltageEN 60204 (PELV)
Standard - Safe isolationDIN VDE 0100-410

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 25;
China RoHSFor details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Dimensions

Width139 mm
Height130 mm
Depth190 mm

Input data

Nominal input voltage range3x 400 V AC - 500 V AC
Input voltage range3x 320 V AC - 575 V AC
Input voltage range2x 360 V AC - 575 V AC (for 2-phase operation)
AC frequency range45 Hz - 65 Hz
Discharge current to PE< 3.5 mA
Current consumption3x 2 A (400 V AC)
Current consumption3x 1.6 A (480 V AC)
Nominal power consumption1387 VA
Inrush surge current< 20 A
Mains buffering> 16 ms (400 V AC)
Mains buffering> 20 ms (480 V AC)
Choice of suitable circuit breakers6 A - 16 A (Characteristics B, C, D, K)
Power factor (cos phi)0.76
Type of protectionTransient surge protection
Protective circuit/componentVaristor

Connection data, input

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.22
Conductor cross section AWG max.10
Stripping length8 mm
Screw threadM3

Connection data, output

Connection methodScrew connection
Conductor cross section solid min.0.5 mm²
Conductor cross section solid max.16 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.10 mm²
Conductor cross section AWG min.8
Conductor cross section AWG max.6
Stripping length10 mm
Screw threadM4

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C - 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport)-40 °C - 85 °C
Max. permissible relative humidity (operation)95 % (at 25 °C, non-condensing)
Climatic class3K3 (in acc. with EN 60721)
Degree of pollution2

Spesso acquistati assieme


Altri articoli da PHOENIX CONTACT

Richiedi un preventivo