Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, input: 1-phase, output: 24 V DC/40 A
Features
For superior system availability
Fast tripping of standard circuit breakers with dynamic power reserve SFB (selective fuse breaking) technology with up to 6 times the nominal current for 12 ms
Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
Preventive function monitoring
BV
cULus Listed
SEMI F47
EAC
cULus Recognized
LR
RINA
NK
IECEE CB Scheme
DNV GL
ABS
CSA
UL Listed
cUL Listed
UL Recognized
cUL Recognized
Specifications
Depth | 125 mm |
---|---|
Height | 130 mm |
Output Voltage | 24 V |
Strip Length | 10 mm |
Voltage | 10 V |
Width | 180 mm |
Ambient conditions | |
Ambient temperature (operation) | -25 °C - 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | 4000 m |
Degree of protection | IP20 |
Output data | |
Nominal output voltage | 24 V DC ±1 % |
Setting range of the output voltage (USet) | 18 V DC - 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 40 A (-25 °C - 60 °C, UOUT = 24 V DC) |
POWER BOOST (IBoost) | 45 A (-25°C - 40°C permanent, UOUT = 24 V DC ) |
Selective Fuse Breaking (ISFB) | 215 A (12 ms) |
Derating | 60 °C - 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback voltage resistance | max. 35 V DC |
Protection against overvoltage at the output (OVP) | < 35 V DC |
Residual ripple | < 30 mVPP (with nominal values) |
Output power | 960 W |
Typical response time | < 0.7 s |
Maximum power dissipation in no-load condition | 14 W |
Power loss nominal load max. | 80 W |
Conformance/approvals | |
UL approvals | UL Listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
UL approvals | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
CSA | CSA-C22.2 No. 107.1-01 |
Shipbuilding approval | DNV GL (EMC A), ABS, LR, RINA, NK, BV |
Standards | |
Standard - Safe isolation | DIN VDE 0100-410 |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard - Equipment safety | BG (design tested) |
Rail applications | EN 50121-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 25; |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Dimensions | |
Width | 180 mm |
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 122 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 183 mm |
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
EMC data | |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Electromagnetic HF field | EN 61000-4-3 |
Frequency range | 80 MHz - 1 GHz |
Test field strength | 20 V/m (Test Level 3) |
Frequency range | 1 GHz - 2 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 2 GHz - 3 GHz |
Comments | Criterion A |
Fast transients (burst) | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Surge voltage load (surge) | EN 61000-4-5 |
Input | 2 kV (Test Level 3 - symmetrical) |
Output | 1 kV (Test Level 2 - symmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz - 80 MHz |
Voltage | 10 V (Test Level 3) |
Wireless telephone simulation | ENV 50204 |
Frequency | 900 MHz |
Frequency | 1800 MHz |
Field intensity | 20 V/m |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Input data | |
Nominal input voltage range | 100 V AC - 240 V AC |
Nominal input voltage range | 120 V DC - 300 V DC (UL 508: ≤ 250 V DC) |
Input voltage range | 85 V AC - 264 V AC |
Input voltage range | 90 V DC - 300 V DC (UL 508: ≤ 250 V DC) |
Dielectric strength maximum | 300 V AC |
AC frequency range | 45 Hz - 65 Hz |
Frequency range DC | 0 Hz |
Discharge current to PE | < 3.5 mA |
Current consumption | 8.8 A (120 V AC) |
Current consumption | 4.6 A (230 V AC) |
Current consumption | 9.5 A (110 V DC) |
Current consumption | 4.7 A (220 V DC) |
Nominal power consumption | 1157 VA |
Inrush current | < 15 A (typical) |
Mains buffering time | > 35 ms (120 V AC) |
Mains buffering time | > 35 ms (230 V AC) |
Input fuse | 20 A (slow-blow, internal) |
Recommended breaker for input protection | 16 A - 20 A (AC: Characteristics B, C, D, K) |
Power factor (cos phi) | 0.88 |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor, gas-filled surge arrester |
Connection data, input | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 14 |
Conductor cross section AWG max. | 10 |
Stripping length | 7 mm |
Screw thread | M3 |
Connection data, output | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.5 mm² |
Conductor cross section solid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 16 mm² |
Conductor cross section AWG min. | 8 |
Conductor cross section AWG max. | 6 |
Stripping length | 10 mm |
Screw thread | M4 |
Connection data for signaling | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 10 |
Screw thread | M3 |