Invia RdO

Inline, Bus coupler, Modbus/RTU, D-SUB-9 female connector, Digital inputs: 8, 24 V DC, connection method: 3-wire, Digital outputs: 4, 24 V DC, 500 mA, connection method: 3-wire, transmission speed in the local bus: 500 kbps / 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields

Features

  • Modbus connection via 9-pos. D-SUB socket

  • Electrical isolation between Modbus interface and logic

  • Eight digital inputs, four digital outputs (on-board)

  • Data transmission speed in Modbus of 1.2 kbps to 115.2 kbps (configurable)

  • Rotary coding switches for setting the Modbus address and for configuration

  • Supported Modbus addresses from 1 to 99

  • Automatic detection of the transmission speed in the local bus (500 kbps or 2 Mbps)

  • Shipbuilding and UL approvals

  • BV

  • EAC

  • ATEX

  • LR

  • DNV GL

  • ABS

  • UL Recognized

  • cUL Recognized

Specifications

Depth71.5 mm
Height119.8 mm
Output Voltage24 V
Width80 mm

Digital outputs

Output nameDigital outputs
Connection methodInline connector
Connection technology3-wire
Number of outputs4
Protective circuitShort-circuit and overload protection Freewheeling circuit in the output driver
Output voltage24 V DC -1 V (At nominal current)
Nominal output voltage24 V DC
Maximum output current per channel500 mA
Maximum output current per module / terminal block2 A
Maximum output current per module2 A
Nominal load, inductive12 VA (1.2 H, 48 Ω)
Nominal load, lamp12 W
Nominal load, ohmic12 W
Limitation of the voltage induced on circuit interruptionapprox. -30 V
Output current when switched offmax. 10 µA (When not loaded, a voltage can be measured even at an output that is not set.)
Behavior with overloadAuto restart
Behavior with inductive overloadOutput can be destroyed
Reverse voltage resistance to short pulsesReverse voltage proof

Interfaces

DesignationModbus/RTU
No. of channels1
Connection methodD-SUB-9 female connector
Note on the connection methodElectrically isolated supply, shielding directly connected to functional earth ground
Transmission speed1.2 kBit/s - 115.2 kBit/s (can be parameterized)
Number of positions9
DesignationInline local bus
Connection methodInline data jumper
Transmission speed500 kbps / 2 Mbps (automatic detection, no combined system)

System limits of the bus coupler

DesignationSystem limits of the bus coupler
Number of supported devicesmax. 63 (per station)
Number of local bus devices that can be connectedmax. 61 (The on-board I/Os are two devices)
Number of devices with parameter channelmax. 8
Number of supported branch terminals with remote bus branch0

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Mechanical testsShock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse
Connection in acc. with standardCUL
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Inline potentials

DesignationBus coupler supply UBC; Communications power UL (7.5 V) and the analog supply UANA (24 V) are generated from the bus coupler supply.
Supply voltage24 V DC (via Inline connector)
Supply voltage range19.2 V DC - 30 V DC (including all tolerances, including ripple)
Current consumptionmin. 80 mA (without connected I/O terminal blocks)
Current consumptionmax. 0.98 A
DesignationCommunications power (UL)
Supply voltage7.5 V DC
Power supply unitmax. 0.8 A DC
DesignationSupply of analog modules (UANA)
Supply voltage24 V DC
Power supply unitmax. 0.5 A DC
DesignationMain circuit supply (UM)
Current consumptionmax. 8 A DC
DesignationSegment circuit supply (US)
Power supply unitmax. 8 A DC (sum of UM + US)
Power consumptiontyp. 1.7 W (entire device)
Current consumptionmin. 6 mA (without connected peripherals)

Dimensions

Width80 mm
Height119.8 mm
Depth71.5 mm
Note on dimensionsSpecfications with connectors

Digital inputs

Input nameDigital inputs
Description of the inputEN 61131-2 type 1
Connection methodInline connector
Connection technology3-wire
Number of inputs8
Typical response timeapprox. 500 µs
Protective circuitReverse polarity protection Suppressor diode
Nominal input voltage UIN24 V DC
Nominal input current at UINtyp. 3 mA
Input voltage24 V DC
Input voltage range "0" signal-30 V DC - 5 V DC
Input voltage range "1" signal15 V DC - 30 V DC
Typical input current per channeltyp. 3 mA
Delay at signal change from 0 to 11.2 ms
Delay at signal change from 1 to 01.2 ms

Ambient conditions

Permissible humidity (storage/transport)10 % - 95 % (non-condensing)
Air pressure (operation)70 kPa - 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20
Ambient temperature (operation)-25 °C - 60 °C
Ambient temperature (storage/transport)-40 °C - 85 °C
Permissible humidity (operation)10 % - 95 % (non-condensing)

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
China RoHSNo hazardous substances above threshold values

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area