Power supply unit - UNO-PS/1AC/24DC/240W - 2904372
- Produttore:
- PHOENIX CONTACT
Primary-switched UNO power supply for DIN rail mounting, input: single-phase, output: 24 V DC/240 W
Features
Flexible mounting by simply snapping onto the DIN rail
More space in the control cabinet with up to 20 % higher power density
Maximum energy efficiency, thanks to over 90 % efficiency and extremely low idling losses under 0.3 W
Outdoor installation, thanks to the wide temperature range from -25°C to +70°C
cULus Listed
EAC
cULus Recognized
IECEE CB Scheme
UL Listed
cUL Listed
UL Recognized
cUL Recognized
Specifications
Depth | 125 mm |
---|---|
Height | 130 mm |
Output Voltage | 24 V |
Strip Length | 8 mm |
Voltage | 10 V |
Width | 45 mm |
Conformance/approvals | |
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
UL approvals | UL/C-UL Recognized UL 60950-1 |
CSA | CAN/CSA-C22.2 No. 60950-1-07 |
CSA | CSA-C22.2 No. 107.1-01 |
CSA | CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 25; |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Standards | |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
Standard - Safety of transformers | EN 61558-2-16 |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage | EN 60950-1 (SELV) and EN 60204 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Mains variation/undervoltage | EN 61000-4-11 |
Dimensions | |
Width | 45 mm |
Height | 130 mm |
Depth | 125 mm |
Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 30 mm / 30 mm |
Output data | |
Nominal output voltage | 24 V DC ±1 % |
Setting range of the output voltage (USet) | 24 V DC - 28 V DC ±1 % |
Nominal output current (IN) | 10 A (-25 °C - 55 °C) |
Derating | 55 °C - 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | No |
Feedback voltage resistance | < 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
Control deviation | change in load, static 10 % - 90 % |
Control deviation | < 2 % (change in load, dynamic 10 % - 90 %) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 50 mVPP (with nominal values) |
Output power | 240 W |
Typical response time | < 1 s |
Maximum power dissipation in no-load condition | < 1.1 W |
Power loss nominal load max. | < 18.8 W |
EMC data | |
Frequency range | 2 GHz - 3 GHz |
Comments | Criterion A |
Fast transients (burst) | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Surge voltage load (surge) | EN 61000-4-5 |
Input | 2 kV (Test Level 3 - symmetrical) |
Output | 1 kV (Test Level 2 - symmetrical) |
Comments | Criterion B |
Conducted interference | EN 61000-4-6 |
Frequency range | 0.15 MHz - 80 MHz |
Voltage | 10 V (Test Level 3) |
Voltage dips | EN 61000-4-11 |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 6 kV (Test Level 3) |
Discharge in air | 8 kV (Test Level 3) |
Electromagnetic HF field | EN 61000-4-3 |
Frequency range | 80 MHz - 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 1 GHz - 2 GHz |
Input data | |
Nominal input voltage range | 100 V AC - 240 V AC |
Input voltage range | 85 V AC - 264 V AC (< 95 V AC Derating 1 %/V) |
Frequency range (fN) | 50 Hz - 60 Hz 10 % |
Current consumption | 2.69 A (100 V AC) |
Current consumption | 1.08 A (240 V AC) |
Nominal power consumption | 260 VA |
Inrush current | < 80 A (typical) |
Mains buffering time | > 10 ms (120 V AC) |
Mains buffering time | > 10 ms (230 V AC) |
Input fuse | 5 A (slow-blow, internal) |
Recommended breaker for input protection | 6 A - 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) | 0.99 |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Connection data, input | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 8 mm |
Screw thread | M3 |
Connection data, output | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 8 mm |
Screw thread | M3 |
Ambient conditions | |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Degree of protection | IP20 |
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
Ambient temperature (operation) | -25 °C - 70 °C (> 55 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) | -40 °C - 85 °C |