Power supply unit - UNO-PS/1AC/24DC/240W - 2904372

Produttore:
PHOENIX CONTACT
Phoenix contact

Df8789adb7951a6e367a26ab7faafae60ade9c10 medium
Codice Nuova Elva
2904372
Codice produttore
2904372
Disponibilità
Invia RdO

Primary-switched UNO power supply for DIN rail mounting, input: single-phase, output: 24 V DC/240 W

Features

  • Flexible mounting by simply snapping onto the DIN rail

  • More space in the control cabinet with up to 20 % higher power density

  • Maximum energy efficiency, thanks to over 90 % efficiency and extremely low idling losses under 0.3 W

  • Outdoor installation, thanks to the wide temperature range from -25°C to +70°C

  • cULus Listed

  • EAC

  • cULus Recognized

  • IECEE CB Scheme

  • UL Listed

  • cUL Listed

  • UL Recognized

  • cUL Recognized

Specifications

Depth125 mm
Height130 mm
Output Voltage24 V
Strip Length8 mm
Voltage10 V
Width45 mm

Conformance/approvals

UL approvalsUL/C-UL listed UL 508
UL approvalsUL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UL approvalsUL/C-UL Recognized UL 60950-1
CSACAN/CSA-C22.2 No. 60950-1-07
CSACSA-C22.2 No. 107.1-01
CSACAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 25;
China RoHSFor details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Standards

EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
Standard - Safety of transformersEN 61558-2-16
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltageEN 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolationDIN VDE 0100-410
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Mains variation/undervoltageEN 61000-4-11

Dimensions

Width45 mm
Height130 mm
Depth125 mm
Installation distance right/left0 mm / 0 mm
Installation distance top/bottom30 mm / 30 mm

Output data

Nominal output voltage24 V DC ±1 %
Setting range of the output voltage (USet)24 V DC - 28 V DC ±1 %
Nominal output current (IN)10 A (-25 °C - 55 °C)
Derating55 °C - 70 °C (2.5%/K)
Connection in parallelYes, for redundancy and increased capacity
Connection in seriesNo
Feedback voltage resistance< 35 V DC
Protection against overvoltage at the output (OVP)≤ 35 V DC
Control deviationchange in load, static 10 % - 90 %
Control deviation< 2 % (change in load, dynamic 10 % - 90 %)
Control deviation< 0.1 % (change in input voltage ±10 %)
Residual ripple< 50 mVPP (with nominal values)
Output power240 W
Typical response time< 1 s
Maximum power dissipation in no-load condition< 1.1 W
Power loss nominal load max.< 18.8 W

EMC data

Frequency range2 GHz - 3 GHz
CommentsCriterion A
Fast transients (burst)EN 61000-4-4
Input4 kV (Test Level 4 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
Surge voltage load (surge)EN 61000-4-5
Input2 kV (Test Level 3 - symmetrical)
Output1 kV (Test Level 2 - symmetrical)
CommentsCriterion B
Conducted interferenceEN 61000-4-6
Frequency range0.15 MHz - 80 MHz
Voltage10 V (Test Level 3)
Voltage dipsEN 61000-4-11
Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Electrostatic dischargeEN 61000-4-2
Contact discharge6 kV (Test Level 3)
Discharge in air8 kV (Test Level 3)
Electromagnetic HF fieldEN 61000-4-3
Frequency range80 MHz - 1 GHz
Test field strength10 V/m (Test Level 3)
Frequency range1 GHz - 2 GHz

Input data

Nominal input voltage range100 V AC - 240 V AC
Input voltage range85 V AC - 264 V AC (< 95 V AC Derating 1 %/V)
Frequency range (fN)50 Hz - 60 Hz 10 %
Current consumption2.69 A (100 V AC)
Current consumption1.08 A (240 V AC)
Nominal power consumption260 VA
Inrush current< 80 A (typical)
Mains buffering time> 10 ms (120 V AC)
Mains buffering time> 10 ms (230 V AC)
Input fuse5 A (slow-blow, internal)
Recommended breaker for input protection6 A - 16 A (Characteristics B, C, D, K)
Power factor (cos phi)0.99
Type of protectionTransient surge protection
Protective circuit/componentVaristor

Connection data, input

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length8 mm
Screw threadM3

Connection data, output

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length8 mm
Screw threadM3

Ambient conditions

Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Climatic class3K3 (in acc. with EN 60721)
Degree of pollution2
Degree of protectionIP20
Inflammability class in acc. with UL 94 (housing / terminal blocks)V0
Ambient temperature (operation)-25 °C - 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport)-40 °C - 85 °C

Spesso acquistati assieme