The E8951 Modbus-to-BACnet protocol converter enables integration of a broad selection of meters, like the PowerLogic BCPM. Supports BACnet IP and Modbus TCP access simultaneously. Compatible with following setup Modbus RTU downstream, BACnet IP, Modbus TCP, SNMP upstream ethernet, BACnet MS/TP or Modbus RTU upstream serial. Specification of the downstream interface 2-wire RS-485 Modbus RTU, can support up to 32 devices. Specification of the upstream ethernet interface 10/100 MB for BACnet IP, Modbus TCP and SNMP protocols. Specification of the upstream serial interface 2-wire RS-485 BACnet MS/TP or Modbus RTU protocols. The gateway need to be supplied with 9 to 30 V DC, or 12 to 24 V AC 50 or 60 Hz. Dimensions of the device are 92 mm in width, 115 mm in heigt and 41 mm in depth. Approved by the following agency CE; TUV approved to UL916; FCC Parc 15 Class A and BTL.

Specifications

CertificationsCE
Current12 V
Depth41 mm
Height129 mm
Number of Outputs0
StandardUL 916
Width74 mm

Specifications

Product Or Component Typeprotocol converter
RangePowerLogic
Communication GatewayModbus to BACnet
Device Applicationgateway
Device Short NameE8951

Complementary

Height129 mm
Range CompatibilityPowerLogic
Width74 mm
Depth41 mm
Number Of Outputs0
Communication Port Protocoldownside Modbus RTU 2-wire RS485 - screw terminal block || upside Modbus TCP ETHERNET - RJ45 || upside BACnet IP ETHERNET - RJ45 || upside BACnet MS/TP 2-wire RS485 - screw terminal block
Maximum Number Of Supported Devices32 Modbus RTU maximum 10000 BACnet data objects
Number Of Inputs0-0
Current Consumption240 mA 12 V
Fixing Modeby clips 35 mm DIN rail) || by screws wall)
[Us] Rated Supply Voltage9...30 V DC || 12...24 V AC
Transmission Rate9.6...38.4 kbauds Modbus RTU downside || 10/100 Mbit/s Modbus TCP upside || 10/100 Mbit/s BACnet IP upside || 9.6, 19.2, 38.4, 76.8 kbauds BACnet MS/TP upside

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX
Eu Rohs DirectiveCompliant

Environment

Product CertificationsCE || TÜV
Ambient Air Temperature For Operation-40-122 °C
StandardsUL 916
Relative Humidity5-90 % without condensation