Modular 3 phase supply control relay, Harmony, 5A, 2CO, 208...440V AC
- Produttore:
- Schneider Electric
This Harmony RM17-TG relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase supply control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. The product monitors its own power supply, when the power supply is abnormal, the output relay de-energizes. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
Specifications
Certifications | C-tick |
---|---|
Housing Material | Plastic |
Net Weight | 0.13 kg |
Operating Cycles | 360 |
Standard | EN/IEC 60255-1 |
Storage Temperature | -40-70 °C |
Warranty Length | 18 months |
Width | 17.5 mm |
Specifications | |
Range Of Product | Harmony Control Relays |
Relay Monitored Parameters | phase sequence || phase failure detection (2 or more phase cut) |
[Uc] Control Circuit Voltage | 208...440 V |
Measurement Range | 208...440 V voltage AC |
Switching Capacity In Va | 1250 VA |
Product Or Component Type | 3-phase control relay |
Relay Name | RM17TG |
Contacts Type And Composition | 2 C/O |
Relay Type | control relay |
Product Specific Application | for 3-phase supply |
Time Delay Type | without |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Voltage Range | 183...484 V |
Marking | CE |
Response Time | <= 130 ms (in the event of a fault) |
Operating Position | any position without derating |
Utilisation Category | AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 |
Net Weight | 0.13 kg |
Maximum Switching Voltage | 250 V AC || 250 V DC |
Measurement Voltage Limits | 183-484 V AC |
Connections - Terminals | screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end |
[Ui] Rated Insulation Voltage | 400 V IEC 60664-1 |
Overvoltage Category | III IEC 60664-1 |
Safety Reliability Data | B10d = 850000 || MTTFd = 924.6 years |
Supply Voltage Limits | 183-484 V AC |
Mounting Support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
Nominal Output Current | 5 A |
Local Signalling | for relay ON LED (yellow) |
Mechanical Durability | 30000000 cycles |
Housing Material | self-extinguishing plastic |
Control Circuit Frequency | 50...60 Hz +/- 10 % |
Width | 17.5 mm |
Tightening Torque | 0.6-1 N.m IEC 60947-1 |
Electrical Durability | 10000 cycles |
Minimum Switching Current | 10 mA 5 V DC |
Run-Up Delay At Power-Up | 650 ms |
Supply Frequency | 50/60 Hz +/- 10 % |
Control Circuit Voltage Limits | 12 % + 10 % Un |
Insulation Resistance | > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1 |
Operating Rate | <= 360 operations/hour full load |
Power Consumption In Va | 0-22 VA 400 V AC 50 Hz |
Output Contacts | 2 C/O |
Voltage Detection Threshold | < 100 V AC |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1504008EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | X |
Circularity Profile | ENVEOLI1504008EN |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Environment | |
Product Certifications | GOST || C-tick || UL || CSA || GL |
Pollution Degree | 3 IEC 60664-1 |
Directives | 73/23/EEC - low voltage directive || 89/336/EEC - electromagnetic compatibility |
Ambient Air Temperature For Storage | -40-70 °C |
Relative Humidity | 95-95 % 55-55 °C IEC 60068-2-30 |
Standards | EN/IEC 60255-1 |
Non-Dissipating Shock Wave | 4 kV |
Dielectric Test Voltage | 2 kV AC 50 Hz, 1 min |
Electromagnetic Compatibility | emission standard for industrial environments EN/IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 || immunity for industrial environments EN/IEC 61000-6-2 |
Shock Resistance | 15 gn 11 ms IEC 60255-21-1 |
Ambient Air Temperature For Operation | -20-50 °C |
Vibration Resistance | 0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1 |
Ip Degree Of Protection | IP20 IEC 60529 terminals) || IP30 IEC 60529 casing) |